Overview

Characteristic

Model Voltage
(V)
Impeller
diameter
(ØCm)
Pole
(P)
Frequency
(Hz)
Current
(A)
OUTPUT
(kW)
Number
of revolutions
(rpm)
Max.Q
(m3/min)
Static
pressure
(mmAq)
Protection
grade
Weight
(Kg)
KTB-012S 1Ø 220 327 2 0.75 50 6.0 2850 22.0 195.0 IP 54 28.5
60 6.2 3450 28.0 265.0
KTB-022S 1Ø 220 327 2 1.5 50 10.8 2850 32.0 205.0 IP 54 35.0
60 12.0 3450 40.0 285.0
KTB-032S 1Ø 220 340 2 2.2 50 12.5 2840 42.0 220.0 IP 54 38.0
60 14.0 3440 52.0 320.0
ETB-012T 3Ø 220/380 327 2 0.75 50 3.5/2.0 2850 22.0 195.0 IP 54 27.5
60 6.5/3.8 3450 40.0 285.0
ETB-022T 3Ø 220/380 327 2 1.5 50 6.2/3.2 2850 22.0 195.0 IP 54 33.0
60 6.5/3.8 3450 40.0 285.0
ETB-032T 3Ø 220/380 340 2 2.2 50 9.0/5.1 2850 42.0 220.0 IP 54 40.0
60 9.2/5.2 3450 52.0 320.0
ETB-052T 3Ø 220/380 380 2 3.7 50 13.0/7.5 2880 52.0 320.0 IP 54 45.0
60 14.0/8.1 3460 63.0 380.0

Blower Installation

(CW)

(CCW)

Reference

  1. The direction of discharge hole of blower is adjustable by every 30 degree for purpose of use.
  2. Set driving unit to reverse side to change discharge(Exhaust) direction, At this instance,Change impeller for reverse direction(Exept radial type)
  3. Impeller is available for
    1) Side horizontal
    2) Side inclined and
    3) Radial type depending on product specification
  4. Radial wing need only replacement of Fan of Product and is used to convey granule of grain or chemical materials

Impeller Standard

turbo_high_temperature_3
turbo_high_temperature_4
Rating(kW) Turbo Impeller(Steel) Radial Impeller(AL)
Impeller
Diameter(Ø)
height(mm) Shaft
Diameter(Ø)
Impeller
Diameter(Ø)
height(mm) Shaft
Diameter(Ø)
0.75 327 64.2 19 300 45 19
1.5 327 80.5 24 327 68 24
2.2 340 110 24 350 72 24
3.7 380 125.5 28 380 78 28
Contact Us

We're not around right now. But you can send us an email and we'll get back to you, asap.